| Power allocator governor tunables
 | |
| =================================
 | |
| 
 | |
| Trip points
 | |
| -----------
 | |
| 
 | |
| The governor works optimally with the following two passive trip points:
 | |
| 
 | |
| 1.  "switch on" trip point: temperature above which the governor
 | |
|     control loop starts operating.  This is the first passive trip
 | |
|     point of the thermal zone.
 | |
| 
 | |
| 2.  "desired temperature" trip point: it should be higher than the
 | |
|     "switch on" trip point.  This the target temperature the governor
 | |
|     is controlling for.  This is the last passive trip point of the
 | |
|     thermal zone.
 | |
| 
 | |
| PID Controller
 | |
| --------------
 | |
| 
 | |
| The power allocator governor implements a
 | |
| Proportional-Integral-Derivative controller (PID controller) with
 | |
| temperature as the control input and power as the controlled output:
 | |
| 
 | |
|     P_max = k_p * e + k_i * err_integral + k_d * diff_err + sustainable_power
 | |
| 
 | |
| where
 | |
|    -  e = desired_temperature - current_temperature
 | |
|    -  err_integral is the sum of previous errors
 | |
|    -  diff_err = e - previous_error
 | |
| 
 | |
| It is similar to the one depicted below::
 | |
| 
 | |
| 				      k_d
 | |
| 				       |
 | |
|   current_temp                         |
 | |
|        |                               v
 | |
|        |              +----------+   +---+
 | |
|        |       +----->| diff_err |-->| X |------+
 | |
|        |       |      +----------+   +---+      |
 | |
|        |       |                                |      tdp        actor
 | |
|        |       |                      k_i       |       |  get_requested_power()
 | |
|        |       |                       |        |       |        |     |
 | |
|        |       |                       |        |       |        |     | ...
 | |
|        v       |                       v        v       v        v     v
 | |
|      +---+     |      +-------+      +---+    +---+   +---+   +----------+
 | |
|      | S |-----+----->| sum e |----->| X |--->| S |-->| S |-->|power     |
 | |
|      +---+     |      +-------+      +---+    +---+   +---+   |allocation|
 | |
|        ^       |                                ^             +----------+
 | |
|        |       |                                |                |     |
 | |
|        |       |        +---+                   |                |     |
 | |
|        |       +------->| X |-------------------+                v     v
 | |
|        |                +---+                               granted performance
 | |
|   desired_temperature     ^
 | |
| 			  |
 | |
| 			  |
 | |
| 		      k_po/k_pu
 | |
| 
 | |
| Sustainable power
 | |
| -----------------
 | |
| 
 | |
| An estimate of the sustainable dissipatable power (in mW) should be
 | |
| provided while registering the thermal zone.  This estimates the
 | |
| sustained power that can be dissipated at the desired control
 | |
| temperature.  This is the maximum sustained power for allocation at
 | |
| the desired maximum temperature.  The actual sustained power can vary
 | |
| for a number of reasons.  The closed loop controller will take care of
 | |
| variations such as environmental conditions, and some factors related
 | |
| to the speed-grade of the silicon.  `sustainable_power` is therefore
 | |
| simply an estimate, and may be tuned to affect the aggressiveness of
 | |
| the thermal ramp. For reference, the sustainable power of a 4" phone
 | |
| is typically 2000mW, while on a 10" tablet is around 4500mW (may vary
 | |
| depending on screen size). It is possible to have the power value
 | |
| expressed in an abstract scale. The sustained power should be aligned
 | |
| to the scale used by the related cooling devices.
 | |
| 
 | |
| If you are using device tree, do add it as a property of the
 | |
| thermal-zone.  For example::
 | |
| 
 | |
| 	thermal-zones {
 | |
| 		soc_thermal {
 | |
| 			polling-delay = <1000>;
 | |
| 			polling-delay-passive = <100>;
 | |
| 			sustainable-power = <2500>;
 | |
| 			...
 | |
| 
 | |
| Instead, if the thermal zone is registered from the platform code, pass a
 | |
| `thermal_zone_params` that has a `sustainable_power`.  If no
 | |
| `thermal_zone_params` were being passed, then something like below
 | |
| will suffice::
 | |
| 
 | |
| 	static const struct thermal_zone_params tz_params = {
 | |
| 		.sustainable_power = 3500,
 | |
| 	};
 | |
| 
 | |
| and then pass `tz_params` as the 5th parameter to
 | |
| `thermal_zone_device_register()`
 | |
| 
 | |
| k_po and k_pu
 | |
| -------------
 | |
| 
 | |
| The implementation of the PID controller in the power allocator
 | |
| thermal governor allows the configuration of two proportional term
 | |
| constants: `k_po` and `k_pu`.  `k_po` is the proportional term
 | |
| constant during temperature overshoot periods (current temperature is
 | |
| above "desired temperature" trip point).  Conversely, `k_pu` is the
 | |
| proportional term constant during temperature undershoot periods
 | |
| (current temperature below "desired temperature" trip point).
 | |
| 
 | |
| These controls are intended as the primary mechanism for configuring
 | |
| the permitted thermal "ramp" of the system.  For instance, a lower
 | |
| `k_pu` value will provide a slower ramp, at the cost of capping
 | |
| available capacity at a low temperature.  On the other hand, a high
 | |
| value of `k_pu` will result in the governor granting very high power
 | |
| while temperature is low, and may lead to temperature overshooting.
 | |
| 
 | |
| The default value for `k_pu` is::
 | |
| 
 | |
|     2 * sustainable_power / (desired_temperature - switch_on_temp)
 | |
| 
 | |
| This means that at `switch_on_temp` the output of the controller's
 | |
| proportional term will be 2 * `sustainable_power`.  The default value
 | |
| for `k_po` is::
 | |
| 
 | |
|     sustainable_power / (desired_temperature - switch_on_temp)
 | |
| 
 | |
| Focusing on the proportional and feed forward values of the PID
 | |
| controller equation we have::
 | |
| 
 | |
|     P_max = k_p * e + sustainable_power
 | |
| 
 | |
| The proportional term is proportional to the difference between the
 | |
| desired temperature and the current one.  When the current temperature
 | |
| is the desired one, then the proportional component is zero and
 | |
| `P_max` = `sustainable_power`.  That is, the system should operate in
 | |
| thermal equilibrium under constant load.  `sustainable_power` is only
 | |
| an estimate, which is the reason for closed-loop control such as this.
 | |
| 
 | |
| Expanding `k_pu` we get::
 | |
| 
 | |
|     P_max = 2 * sustainable_power * (T_set - T) / (T_set - T_on) +
 | |
| 	sustainable_power
 | |
| 
 | |
| where:
 | |
| 
 | |
|     - T_set is the desired temperature
 | |
|     - T is the current temperature
 | |
|     - T_on is the switch on temperature
 | |
| 
 | |
| When the current temperature is the switch_on temperature, the above
 | |
| formula becomes::
 | |
| 
 | |
|     P_max = 2 * sustainable_power * (T_set - T_on) / (T_set - T_on) +
 | |
| 	sustainable_power = 2 * sustainable_power + sustainable_power =
 | |
| 	3 * sustainable_power
 | |
| 
 | |
| Therefore, the proportional term alone linearly decreases power from
 | |
| 3 * `sustainable_power` to `sustainable_power` as the temperature
 | |
| rises from the switch on temperature to the desired temperature.
 | |
| 
 | |
| k_i and integral_cutoff
 | |
| -----------------------
 | |
| 
 | |
| `k_i` configures the PID loop's integral term constant.  This term
 | |
| allows the PID controller to compensate for long term drift and for
 | |
| the quantized nature of the output control: cooling devices can't set
 | |
| the exact power that the governor requests.  When the temperature
 | |
| error is below `integral_cutoff`, errors are accumulated in the
 | |
| integral term.  This term is then multiplied by `k_i` and the result
 | |
| added to the output of the controller.  Typically `k_i` is set low (1
 | |
| or 2) and `integral_cutoff` is 0.
 | |
| 
 | |
| k_d
 | |
| ---
 | |
| 
 | |
| `k_d` configures the PID loop's derivative term constant.  It's
 | |
| recommended to leave it as the default: 0.
 | |
| 
 | |
| Cooling device power API
 | |
| ========================
 | |
| 
 | |
| Cooling devices controlled by this governor must supply the additional
 | |
| "power" API in their `cooling_device_ops`.  It consists on three ops:
 | |
| 
 | |
| 1. ::
 | |
| 
 | |
|     int get_requested_power(struct thermal_cooling_device *cdev,
 | |
| 			    struct thermal_zone_device *tz, u32 *power);
 | |
| 
 | |
| 
 | |
| @cdev:
 | |
| 	The `struct thermal_cooling_device` pointer
 | |
| @tz:
 | |
| 	thermal zone in which we are currently operating
 | |
| @power:
 | |
| 	pointer in which to store the calculated power
 | |
| 
 | |
| `get_requested_power()` calculates the power requested by the device
 | |
| in milliwatts and stores it in @power .  It should return 0 on
 | |
| success, -E* on failure.  This is currently used by the power
 | |
| allocator governor to calculate how much power to give to each cooling
 | |
| device.
 | |
| 
 | |
| 2. ::
 | |
| 
 | |
| 	int state2power(struct thermal_cooling_device *cdev, struct
 | |
| 			thermal_zone_device *tz, unsigned long state,
 | |
| 			u32 *power);
 | |
| 
 | |
| @cdev:
 | |
| 	The `struct thermal_cooling_device` pointer
 | |
| @tz:
 | |
| 	thermal zone in which we are currently operating
 | |
| @state:
 | |
| 	A cooling device state
 | |
| @power:
 | |
| 	pointer in which to store the equivalent power
 | |
| 
 | |
| Convert cooling device state @state into power consumption in
 | |
| milliwatts and store it in @power.  It should return 0 on success, -E*
 | |
| on failure.  This is currently used by thermal core to calculate the
 | |
| maximum power that an actor can consume.
 | |
| 
 | |
| 3. ::
 | |
| 
 | |
| 	int power2state(struct thermal_cooling_device *cdev, u32 power,
 | |
| 			unsigned long *state);
 | |
| 
 | |
| @cdev:
 | |
| 	The `struct thermal_cooling_device` pointer
 | |
| @power:
 | |
| 	power in milliwatts
 | |
| @state:
 | |
| 	pointer in which to store the resulting state
 | |
| 
 | |
| Calculate a cooling device state that would make the device consume at
 | |
| most @power mW and store it in @state.  It should return 0 on success,
 | |
| -E* on failure.  This is currently used by the thermal core to convert
 | |
| a given power set by the power allocator governor to a state that the
 | |
| cooling device can set.  It is a function because this conversion may
 | |
| depend on external factors that may change so this function should the
 | |
| best conversion given "current circumstances".
 | |
| 
 | |
| Cooling device weights
 | |
| ----------------------
 | |
| 
 | |
| Weights are a mechanism to bias the allocation among cooling
 | |
| devices.  They express the relative power efficiency of different
 | |
| cooling devices.  Higher weight can be used to express higher power
 | |
| efficiency.  Weighting is relative such that if each cooling device
 | |
| has a weight of one they are considered equal.  This is particularly
 | |
| useful in heterogeneous systems where two cooling devices may perform
 | |
| the same kind of compute, but with different efficiency.  For example,
 | |
| a system with two different types of processors.
 | |
| 
 | |
| If the thermal zone is registered using
 | |
| `thermal_zone_device_register()` (i.e., platform code), then weights
 | |
| are passed as part of the thermal zone's `thermal_bind_parameters`.
 | |
| If the platform is registered using device tree, then they are passed
 | |
| as the `contribution` property of each map in the `cooling-maps` node.
 | |
| 
 | |
| Limitations of the power allocator governor
 | |
| ===========================================
 | |
| 
 | |
| The power allocator governor's PID controller works best if there is a
 | |
| periodic tick.  If you have a driver that calls
 | |
| `thermal_zone_device_update()` (or anything that ends up calling the
 | |
| governor's `throttle()` function) repetitively, the governor response
 | |
| won't be very good.  Note that this is not particular to this
 | |
| governor, step-wise will also misbehave if you call its throttle()
 | |
| faster than the normal thermal framework tick (due to interrupts for
 | |
| example) as it will overreact.
 | |
| 
 | |
| Energy Model requirements
 | |
| =========================
 | |
| 
 | |
| Another important thing is the consistent scale of the power values
 | |
| provided by the cooling devices. All of the cooling devices in a single
 | |
| thermal zone should have power values reported either in milli-Watts
 | |
| or scaled to the same 'abstract scale'.
 |